Electrical Product Agents
Description
240VDC?Battery?Voltage?High?Frequency?Online?UPS?Single?Phase?10KVA
?
?
Quick Detail:
?
# 240VDC?battery?voltage
# Crest?factor:3:1
# Input:(120±5)VAC~?(275±5)VAC
# Output:220Vac
# Rate Capacity:6K-240VDC?battery?voltage
# Power factor:0.8
?
?
Specifications:
?
- - - -
Model | VT6K | VT6KS | VT10K | VT10KS |
Rating | 6KVA/4800W | 10KVA/8000W |
Input | Input?system | Single?phase?&?earth?ground |
Voltage?range | (120±5)VAC~?(275±5)VAC |
Power?factor | ≥0.99 |
Voltage?range?of?bypass | (60±5)VAC~?(300±5)VAC?(default:?60VAC~300VAC?
Could?be?adjusted?by?software) |
Output | Output?system | Single?phase?&?earth?ground |
Rated?voltage | 220VAC??① |
Power?factor | 0.8 |
Voltage?precision | ±1% |
Output?frequency | Normal?mode | 1.The?output?frequency?synchronizes?with?the?input?frequency?
when?the?input?frequency?is?in?the?range?of??46?Hz~?54?Hz
2.The?output?frequency?is?50Hz?when?the?input
?frequency?is?not?in?the?range?of?46?Hz~?54?Hz
3.Can?be?set?as?60Hz |
Battery?mode |
Inverter?overload?capacity
?(Utility?power,?25℃) | 105%±5%
Transfer?time | 0ms?(Normal?mode←→?Battery?mode) |
<4ms?(Normal?mode←→Bypass?mode) |
Crest?factor | 3:1 |
Battery | Batteries?voltage | 192VDC |
Battery?quantity | 16????② |
Battery?Type | Sealed?maintenance-free?lead?–acid?battery?
of?battery?voltage?12V/7AH |
Backup?Time?(25℃) | Full?load≥5min?(Standard) |
Charge?current | Standard??1A | Long??6.5A |
①?Note1:?Output?voltage?can?be?set:?200V/208V/220V/230V/240V.
②?Note2:?240VDC?battery?voltage?can?be?choose |
- - - -
?
?
Zero power switch delay: When the utility power fails, UPS will automatically switch from AC mode to battery mode with no delay, which ensures stable power supply of operating system.
Active Load Management: This technology allows the UPS to be set up at a fixed 50Hz or 60Hz output, while it also can intelligently monitor power usage and automatically sheds and reconnects loads in order to prevent generator overload.
Sufficient Expansion Slots: The pre-allocated smart slots enable flexibility in choice of USB cards,AS400 cards, CMC monitoring cards, SNMP cards, RS485 cards and EMD environment monitoring cards.
The load power factor is 0.8: it adapts the features of most current electric equipment and elevates the load-bearing capacity of the machines.
Generator Supportable:The wide range of input voltage and frequency can effectively separate the harmful electric wave produces by the generators and provide safe and reliable power supply.
?
?
?
Read More
Shenzhen Ada Power Electronics Co.,Limited
Low Voltage Variable Frequency Drive,Solar Variable Frequency Drive,3 Phase Variable Frequency Drive
Address: Xinzhong Road Baishi Zhou Nanshan District,
Shenzhen, Guangdong
China, 518000
Tel: 86-755-86099322
Fax: 86-755-86099322