Electronic Signs
Description
Practical CO2 controller with relay output and 3 LED indicators Specifications
- - - -
Gas detected | Carbon Dioxide (CO2) |
Sensing element | Non-Depressive Infrared Detector (NDIR) |
Temperature sensor | NTC |
Temperature correction | Self compensation |
CO2 NDIR life | 15 years |
Consumption | 3.5W/ Max, 2.5W/ Average |
Accuracy@25℃(77℉) | ±40ppm + 3% of reading |
Stability | <2% of FS over life of sensor (15 yr typical) |
Warm up time | 2 hours (first time) 2 minutes (operation) |
CO2 measuring range | 0~5,000ppm(default ), ?0~2,000ppm programmable selection |
CO2 setting & Display resolution | 1ppm |
Temperature measuring range | 0~50℃(32~122℉) |
Temperature setting range | 5~45℃(41~113℉) |
Option: 1X dry contact output | Rated currency for contact point: 2A 220VAC/30VDC, resistance load |
Option: RS485 communication interface | 9600/14400/19200(default)/28800/38400bps rates selectable by program,15KV protection for static, independent address setting? |
Operation condition | 0~50℃ (32~122℉), 0~95%RH without condensing |
Power supply | 220VAC/110VAC or 24VAC? 50/60HZ±10% |
Weight | 380g |
Dimensions | 130mm×90mm×40mm |
Connections Interface | Locate in interface of connection |
Installment standard | 65mm×65mm or 2”×4” wire box |
Wiring standard | Wire section area<1.5mm2 |
Approval Standard | CE-Approval |
Programming and selection | DIP switches inside and external push-buttons |
- - - -
?
Features
?
1. Real-time detecting and display CO2 level during 0ppm to 20,000ppm CO2 range; Also detecting room temperature from 5 to 45℃
2. Optional real-time humidity from 5%RH to 95%RH
3. NDIR CO2 sensor technology of infrared self diffusion, 15 years lifetime
4. Self Calibration Algorithm makes it in using without calibration amending
5. The three measured CO2 ranges for 3-LED indicator lights selectable by end users
6. LED’s brightness adjustment
7. Optional 1X dry contact output or one 0~10VDC output to control a ventilation device
8. Easy preset CO2 level for buzzer alert (optional)
9. Optional RS485 interface to connect to a PC or another system (optional)
?
?
Buttons and LCD
?
?
Mounting and dimensions
?
?
?
Wiring Diagram
?
?
?
Model Guide
?
?
Note: X2 + X3 ≤1
Example: F2000IAQ-CO2-3100 indicates that it is a CO2 indicator with temperature detection.
?
Read More
Tongdy Control Technology Co., Ltd
CO2 Monitor,CO2 Controller,CO2 Transmitter
Address: Building #8, Courtyard #9, Dijin Rd., Haidian Dist., Beijing 100095, China,
Beijing, Beijing
China, 100095
Tel: 86-10-59738930
Fax: 86-10-59738935